ContaminationSensor CS 1000 Status Messages
HYDAC FILTER SYSTEMS GMBH
en(us)
Page 87/112
BeWa CS1000 3764916 300 en-us 2012-08-29.doc 2012-08-29
LED Blink code /
Display /
Analog output /
Switch out
Status To do
Error
no.
Red
<)<(</
2CLEAN
Current value mA / V*
Conductive
The sensor is below
its measurement
range ISO 9/8/7
---
-
error
LED Blink code /
Display /
Analog output /
Switch out
Status To do
Error
no.
Red
CHECK
19,9 mA / 9,95 V*
Open
It is not possible to
determine the flow
rate.
The sensor status is
undefined.
Check that the flow is
between 30 … 500
ml/min.
If the fluid cleanliness
is below the
measurement limit
(ISO 9/8/7), it may
take several
measurement cycles
until measured
values are displayed.